Ventilation Rate Calculator

Work out the ventilation a room or home needs under Approved Document F. Choose an extract fan for one room or the whole home, enter the size, and press Calculate to see the rate in litres per second, cubic metres per hour and air changes per hour.

What Do You Need?

Room

Type Of Fan

Size Of The Room

m
m
m

Used for the air changes per hour.

Figures are the minimum rates in Approved Document F 2021 (England). Fans must be installed and commissioned to reach them.

How To Use The Ventilation Rate Calculator

  1. Choose what you need: an extract fan for one room, or the ventilation rate for the whole home.
  2. For one room, pick the room and whether the fan is switched on and off (intermittent) or runs all the time (continuous), and enter the room size.
  3. For the whole home, enter the number of bedrooms, the total floor area and the number of bathrooms, separate WCs and utility rooms.
  4. Press Calculate Ventilation.

You get the minimum rate in litres per second (l/s), the same in cubic metres per hour (m³/h), which is how most fans are sold, and the air changes per hour for the room or home. A drawing shows the air in and out, a table lists the Approved Document F rates, and you can copy the result or save it as a PDF.

Extract Fan Rates By Room

In England, Approved Document F (2021 edition, Volume 1: Dwellings) sets the minimum extract rates for kitchens, bathrooms, utility rooms and WCs:

RoomIntermittent FanContinuous FanIntermittent In m³/h
Kitchen, cooker hood over the hob30 l/s13 l/s108 m³/h
Kitchen, fan elsewhere60 l/s13 l/s216 m³/h
Utility room30 l/s8 l/s108 m³/h
Bathroom or shower room15 l/s8 l/s54 m³/h
WC only6 l/s6 l/s22 m³/h

A kitchen fan away from the hob needs twice the rate of a cooker hood over it, because a hood catches steam and fumes at the source. The hood must extract to outside: a recirculating hood filters the air and puts it back, so it does not count as extract ventilation. A continuous fan runs at the lower rate all the time and needs a boost setting for when the room is in use.

Whole Home Ventilation Rate

The whole home rate is the fresh air the home needs all the time to keep moisture and pollutants down. Under Approved Document F 2021 it is the greater of a figure based on the number of bedrooms and 0.3 l/s for each square metre of internal floor area, counting every floor.

BedroomsRate (l/s)Rate (m³/h)
11968
22590
331112
437133
543155

The table assumes two people in the main bedroom and one in each other bedroom. For more than five bedrooms, the calculator continues the table’s pattern of 6 l/s per bedroom; check Approved Document F for larger homes. Zehnder’s summary of the regulations compares the 2021 figures with the older ones, which were lower.

l/s, m³/h And Air Changes

m³/h = l/s × 3.6 · air changes per hour = m³/h ÷ room volume (m³)

Building Regulations give rates in litres per second, but most fans are sold in cubic metres per hour, so multiply by 3.6. A bathroom fan of 15 l/s must move at least 54 m³/h. Air changes per hour show how many times the air in the room is replaced each hour: 54 m³/h in a 12 m³ bathroom is 4.5 air changes an hour. Approved Document F does not set air changes for homes, but they are a useful check on how hard a fan is working in a large or small room.

Intermittent Fans Or Continuous Ventilation?

  • Intermittent extract fans switch on with the light or a humidity sensor in each wet room, with background ventilators such as trickle vents in the windows for the rest of the time. Fans in rooms without an openable window should run on for 15 minutes after the room is used.
  • Continuous mechanical extract (MEV) runs quietly all the time in each wet room, boosting when needed. The total continuous extract must be at least the whole home rate.
  • Mechanical ventilation with heat recovery (MVHR) extracts from wet rooms and supplies fresh air to living rooms and bedrooms, passing it through a heat exchanger to save heat. It suits very airtight homes.

In whole home mode, the calculator gives the total continuous extract and the set of intermittent fans for your home, so you can compare the two approaches.

Choosing And Fitting An Extract Fan

  1. Pick a fan rated above the minimum, as the flow quoted on the box falls with long or bendy ducts and outside grilles.
  2. Fit it high up and as far from the door or main air inlet as possible, so fresh air crosses the room.
  3. Leave a gap under the door, about 10 mm above the floor finish, so air can get in to replace what the fan removes.
  4. Keep ducts short and straight, and insulate them where they pass through a cold loft to stop condensation.
  5. In a bathroom, keep the fan out of the zones near the bath or shower unless it is rated for them, and have the wiring done by a qualified electrician.

Ventilation affects heat loss too: see our heat loss calculator for the heat a room needs, including the air leaving through fans and vents.

Worked Examples

Bathroom fan: a 2.5 × 2 m bathroom, 2.4 m high, with an intermittent fan.

  • Minimum rate: 15 l/s, which is 15 × 3.6 = 54 m³/h.
  • Volume 2.5 × 2 × 2.4 = 12 m³, so 54 ÷ 12 = 4.5 air changes per hour.

Whole home: a three-bedroom house of 90 m² with one bathroom and a separate WC.

  • By bedrooms: 31 l/s. By floor area: 90 × 0.3 = 27 l/s. The whole home rate is the greater, 31 l/s or 112 m³/h.
  • Continuous extract from the kitchen (13), bathroom (8) and WC (6) adds up to 27 l/s, so an MEV system must be set to at least 31 l/s in total.

How The Calculator Works

Room rates come straight from the Approved Document F 2021 tables for intermittent and continuous extract. The whole home rate is the larger of the bedroom figure and 0.3 l/s per m² of floor area. Continuous extract adds 13 l/s for the kitchen, 8 for each bathroom and utility room and 6 for each separate WC, and the system total is the larger of that and the whole home rate. Rates are converted at 3.6 m³/h per l/s, and air changes use the room or home volume from your ceiling height. These are minimum rates for England; Wales, Scotland and Northern Ireland have their own guidance.

Ventilation FAQs

What size extract fan do I need for a bathroom?

At least 15 l/s, or 54 m³/h, for an intermittent fan under Approved Document F 2021, or 8 l/s for a continuous fan.

What extract rate does a kitchen need?

30 l/s (108 m³/h) for a cooker hood over the hob that extracts to outside, or 60 l/s (216 m³/h) for a fan elsewhere in the kitchen.

How do I convert l/s to m³/h?

Multiply by 3.6. 15 l/s is 54 m³/h and 30 l/s is 108 m³/h.

What is the whole house ventilation rate for a 3-bed house?

At least 31 l/s, or 0.3 l/s per m² of floor area if that is more.

Does a recirculating cooker hood count?

No. It does not extract air to outside, so the kitchen still needs extract ventilation.

Does a bathroom fan need an overrun timer?

Where the room has no openable window, an intermittent fan should run on for 15 minutes after use.

How many air changes per hour does a bathroom need?

Approved Document F sets rates in l/s rather than air changes. A 15 l/s fan in a typical 12 m³ bathroom gives about 4.5 air changes per hour.

What is the extract rate for a utility room?

30 l/s intermittent or 8 l/s continuous.

More Calculators

Extract and whole home rates from Approved Document F 2021, Volume 1: Dwellings, as summarised by Zehnder and Nuaire. Reviewed November 2026.